XLPE Insulated Power Cable
This product is suitable for transmission and distribution system at the voltage from LV to MV. The power cables can be flame retardant when used as type ZR.
About this product
Product information from the supplier.




Installation Temperature: The installation temperature should be over 0℃. If the ambient temperature is lower than 0℃, the cable should be preheated.
Operating Temperature: Max permissible continuous operating temperature of the conductor shall not exceed 90℃.
Conductor Short-circuit Temperature: Max temperature at short-circuit shall not exceed 250℃ . The short-circuit duration shall not exceed 5 seconds.
Bending Radius: 20( d+D) +/-5% for single core cable,15( d+D )+/-5% for multi-core cable.
D=Actual outer diameter of cable (mm),d=Actual diameter of the conductor (mm)
Standard: IEC60502, GB/T12706, or other standard required by the customer. The requirements for flame retardant property are according to IEC60332-3 and GB18380.
Packing: Steel/wooden reel, wooden reel, or steel reel.

|
Description |
Application |
|
Cu or Al conductor/ XLPE insulated/ PVC sheathed power cable |
It is installed in indoor or outdoor,and can be pulled with a proper force during installation ,but unable to bear external mechanical force.Single core cable is not permitted to install in magnetic duct. |
|
Cu or Al conductor/ XLPE insulated/ PVC sheathed flame retardant power cable |
|
|
Cu or Al conductor/ XLPE insulated/ steel tape armored/ PVC sheathed power cable |
It is installed under ground and able to bear external mechanical force,but unable to bear large pulling force. |
|
Cu or Al conductor/ XLPE insulated steel tape armored/ PVC sheathed flame retardant power cable |
|
|
Cu or Al conductor/ XLPE insulated/ steel wire armored/ PVC sheathed power cable |
It is installed under water or where the cable route is with large difference of level.It is able to bear external mechanical force and proper pulling force. |
|
Cu or Al conductor/ XLPE insulated/ steel wire armored/ PVC sheathed flame retardant power cable |

|
Type |
No of Cores |
Rated Voltage (kV) |
||||||
|
0.6/1 |
3.6/6 |
6/6 6/10 |
8.7/10 8.7/15 |
12/20 |
21/35 |
26/35 26/45 |
||
|
Nominal Area of Conductor (sq.mm) |
||||||||
|
CU or AL/XLPE/PVC |
1 |
1.5 to 240 |
25 to 500 |
25 to 500 |
25 to 500 |
35 to 500 |
50 to 500 |
50 to 500 |
|
3 |
1.5 to 240 |
25 to 300 |
25 to 300 |
25 to 300 |
35 to 300 |
--- |
--- |
|
|
CU or AL/XLPE/STA/PVC |
3 |
10 to 240 |
25 to 300 |
25 to 300 |
25 to 300 |
35 to 300 |
--- |
--- |
|
CU or AL/XLPE/SWA/PVC |
3 |
10 to 240 |
25 to 300 |
25 to 300 |
25 to 300 |
35 to 300 |
--- |
--- |
*1kV 4-core XLPE cable is also in our supply range.

Construction of 0.6/1 kV 1-core
CU or AL/XLPE Insulated/ PVC Sheathed Power Cable

|
No |
Construction and materials |
|
1 |
Copper or aluminum conductor |
|
2 |
XLPE insulation |
|
3 |
Non-flame retardant or flame retardant PVC sheath |
Technical Characteristics of 0.6/1kV for CU or AL conductor/XLPE Insulated/PVC Sheathed Power Cable, 1-core
|
Nominal conductor cross section area (mm) |
Nominal Insulation thickness (mm) |
Nominal sheath thickness (mm) |
Approx Overall Diameter (mm) |
Max DC Conductor resistance at 20C (Ω/km) |
Approx weight of cable (kg/km) |
||
|
Cu |
Al |
Cu |
Al |
||||
|
1x 1.5 |
0.7 |
1.5 |
6 |
12.1 |
--- |
53 |
--- |
|
1x2.5 |
0.7 |
1.5 |
6 |
7.41 |
12.1 |
68 |
53 |
|
1x4 |
0.7 |
1.5 |
7 |
4.61 |
7.41 |
87 |
64 |
|
1x6 |
0.7 |
1.5 |
7 |
3.08 |
4.61 |
110 |
73 |
|
1x10 |
0.7 |
1.5 |
8 |
1.83 |
3.08 |
155 |
95 |
|
1x16 |
0.7 |
1.5 |
9 |
1.15 |
1.91 |
220 |
120 |
|
1x25 |
0.9 |
1.5 |
10 |
0.727 |
1.20 |
345 |
190 |
|
1x35 |
0.9 |
1.5 |
12 |
0.524 |
0.868 |
424 |
207 |
|
1x50 |
1.0 |
1.5 |
13 |
0.387 |
0.641 |
555 |
245 |
|
1x70 |
1.1 |
1.5 |
14 |
0.268 |
0.443 |
770 |
336 |
|
1x95 |
1.1 |
1.5 |
16 |
0.193 |
0.320 |
1040 |
455 |
|
1x 120 |
1.2 |
1.5 |
18 |
0.153 |
0.253 |
1290 |
550 |
|
1x 150 |
1.4 |
2.0 |
21 |
0.124 |
0.206 |
1590 |
650 |
|
1x 185 |
1.6 |
2.0 |
23 |
0.0991 |
0.164 |
1944 |
804 |
|
1x240 |
1.7 |
2.0 |
25 |
0.0754 |
0.125 |
2510 |
1021 |
Construction of 3.6/6kV to 26/35kV, 1- core, CU or AL conductor/XLPE Insulated/ PVC Sheathed Power Cable

|
No |
Construction and materials |
|
1 |
Copper or aluminum conductor |
|
2 |
Semi-conductive conductor screen |
|
3 |
XLPE insulation |
|
4 |
Semi-conductive insulation screen |
|
5 |
Copper tape screen |
|
6 |
Non-woven cloth tape or glass fiber tape |
|
7 |
Non-flame retardant or flame retardant PVC sheath |
Technical Characteristics of 3.6/6kV for CU or AL conductor/XLPE Insulated /PVC Sheathed Power Cable, 1-core
|
Nominal conductor cross section area (mm) |
Nominal Insulation thickness (mm) |
Nominal sheath thickness (mm) |
Approx Overall Diameter (mm) |
Max DC Conductor resistance at 20C (Ω/km) |
Approx weight of cable (kg/km) |
||
|
Cu |
Al |
Cu |
Al |
||||
|
1x25 |
2.5 |
1.5 |
19 |
0.727 |
1.20 |
576 |
421 |
|
1x35 |
2.5 |
1.5 |
20 |
0.524 |
0.868 |
695 |
479 |
|
1x50 |
2.5 |
2.0 |
21 |
0.387 |
0.641 |
860 |
550 |
|
1x70 |
2.5 |
2.0 |
23 |
0.268 |
0.443 |
1081 |
648 |
|
1x95 |
2.5 |
2.0 |
24 |
0.193 |
0.320 |
1350 |
762 |
|
1x 120 |
2.5 |
2.0 |
26 |
0.153 |
0.253 |
1640 |
897 |
|
1x 150 |
2.5 |
2.0 |
27 |
0.124 |
0.206 |
1947 |
1079 |
|
1x 185 |
2.5 |
2.0 |
29 |
0.0991 |
0.164 |
2302 |
1156 |
|
1x240 |
2.6 |
2.0 |
32 |
0.0754 |
0.125 |
2886 |
1400 |
|
1x300 |
2.8 |
2.0 |
34 |
0.0601 |
0.100 |
3483 |
1626 |
|
1x400 |
3.0 |
2.5 |
38 |
0.047 |
0.0778 |
4477 |
2001 |
|
1x500 |
3.2 |
2.5 |
41 |
0.0366 |
0.0605 |
5452 |
2357 |
Technical Characteristics of 6/6kV,6/10kV for CU or AL conductor/XLPE Insulated /PVC Sheathed Power Cable, 1-core
|
Nominal conductor cross section area (mm) |
Nominal Insulation thickness (mm) |
Nominal sheath thickness (mm) |
Approx Overall Diamete (mm) |
Max DC Conductor resistance at 20C (Ω/km) |
Approx weight of cable (kg/km) |
||
|
Cu |
Al |
Cu |
Al |
||||
|
1x25 |
3.4 |
2.0 |
20 |
0.727 |
1.20 |
598 |
443 |
|
1x35 |
3.4 |
2.0 |
22 |
0.524 |
0.868 |
719 |
502 |
|
1x50 |
3.4 |
2.0 |
23 |
0.387 |
0.641 |
884 |
575 |
|
1x70 |
3.4 |
2.0 |
24 |
0.268 |
0.443 |
1097 |
664 |
|
1x95 |
3.4 |
2.0 |
26 |
0.193 |
0.320 |
1378 |
790 |
|
1x 120 |
3.4 |
2.0 |
28 |
0.153 |
0.253 |
1658 |
916 |
|
1x 150 |
3.4 |
2.0 |
30 |
0.124 |
0.206 |
1967 |
1038 |
|
1x 185 |
3.4 |
2.0 |
31 |
0.0991 |
0.164 |
2335 |
1190 |
|
1x240 |
3.4 |
2.0 |
34 |
0.0754 |
0.125 |
2908 |
1423 |
|
1x300 |
3.4 |
2.0 |
36 |
0.0601 |
0.100 |
3507 |
1650 |
|
1x400 |
3.4 |
2.5 |
39 |
0.0470 |
0.0778 |
4503 |
2027 |
|
1x500 |
3.4 |
2.5 |
42 |
0.0366 |
0.0605 |
5479 |
2384 |
Technical Characteristics of 8.7/10kV,8.7/15kV for CU or AL conductor/XLPE Insulated /PVC Sheathed Power Cable, 1-core
|
Nominal conductor cross section area (mm) |
Nominal Insulation thickness (mm) |
Nominal sheath thickness (mm) |
Approx Overall Diameter (mm) |
Max DC Conductor resistance at 20C (Ω/km) |
Approx weight of cable (kg/km) |
||
|
Cu |
Al |
Cu |
Al |
||||
|
1x25 |
4.5 |
1.8 |
23 |
0.727 |
1.20 |
680 |
525 |
|
1x35 |
4.5 |
1.8 |
24 |
0.524 |
0.868 |
804 |
587 |
|
1x50 |
4.5 |
1.9 |
25 |
0.387 |
0.641 |
984 |
674 |
|
1x70 |
4.5 |
1.9 |
27 |
0.268 |
0.443 |
1201 |
768 |
|
1x95 |
4.5 |
2.0 |
29 |
0.193 |
0.320 |
1490 |
902 |
|
1x 120 |
4.5 |
2.0 |
30 |
0.153 |
0.253 |
1765 |
1022 |
|
1x 150 |
4.5 |
2.1 |
32 |
0.124 |
0.206 |
2091 |
1162 |
|
1x 185 |
4.5 |
2.1 |
34 |
0.0991 |
0.164 |
2452 |
1307 |
|
1x240 |
4.5 |
2.2 |
36 |
0.0754 |
0.125 |
3034 |
1548 |
|
1x300 |
4.5 |
2.4 |
39 |
0.0601 |
0.100 |
3672 |
1815 |
|
1x400 |
4.5 |
2.4 |
42 |
0.047 |
0.0778 |
4646 |
2170 |
|
1x500 |
4.5 |
2.5 |
45 |
0.0366 |
0.0605 |
5651 |
2556 |
Technical Characteristics of 12/20kVfor CU or AL conductor/XLPE Insulated /PVC Sheathed Power Cable, 1-core
|
Nominal conductor cross section area (mm) |
Nominal Insulation thickness (mm) |
Nominal sheath thickness (mm) |
Approx Overall Diameter (mm) |
Max DC Conductor resistance at 20C (Ω/km) |
Approx weight of cable (kg/km) |
||
|
Cu |
Al |
Cu |
Al |
||||
|
1x35 |
5.5 |
2.0 |
27 |
0.524 |
0.868 |
979 |
762 |
|
1x50 |
5.5 |
2.0 |
29 |
0.387 |
0.641 |
1155 |
846 |
|
1x70 |
5.5 |
2.0 |
30 |
0.268 |
0.443 |
1393 |
959 |
|
1x95 |
5.5 |
2.0 |
32 |
0.193 |
0.320 |
1681 |
1093 |
|
1x 120 |
5.5 |
2.0 |
34 |
0.153 |
0.253 |
1979 |
1236 |
|
1x 150 |
5.5 |
2.0 |
35 |
0.124 |
0.206 |
2301 |
1373 |
|
1x 185 |
5.5 |
2.0 |
38 |
0.0991 |
0.164 |
2718 |
1573 |
|
1x240 |
5.5 |
2.5 |
40 |
0.0754 |
0.125 |
3302 |
1817 |
|
1x300 |
5.5 |
2.5 |
43 |
0.0601 |
0.100 |
3941 |
2084 |
|
1x400 |
5.5 |
2.5 |
45 |
0.0470 |
0.0778 |
4931 |
2455 |
|
1x500 |
5.5 |
2.5 |
48 |
0.0366 |
0.0605 |
5956 |
2861 |
Technical Characteristics of 21/35kVfor CU or AL conductor/XLPE Insulated /PVC Sheathed Power Cable, 1-core
|
Nominal conductor cross section area (mm) |
Nominal Insulation thickness (mm) |
Nominal sheath thickness (mm) |
Approx Overall Diameter (mm) |
Max DC Conductor resistance at 20C (Ω/km) |
Approx weight of cable (kg/km) |
||
|
Cu |
Al |
Cu |
Al |
||||
|
1x50 |
9.3 |
2.0 |
37 |
0.387 |
0.641 |
1609 |
1360 |
|
1x70 |
9.3 |
2.5 |
38 |
0.268 |
0.443 |
1850 |
1417 |
|
1x95 |
9.3 |
2.5 |
40 |
0.193 |
0.320 |
2193 |
1605 |
|
1x 120 |
9.3 |
2.5 |
42 |
0.153 |
0.253 |
2498 |
1756 |
|
1x 150 |
9.3 |
2.5 |
44 |
0.124 |
0.206 |
2839 |
1910 |
|
1x 185 |
9.3 |
2.5 |
45 |
0.0991 |
0.164 |
3248 |
2102 |
|
1x240 |
9.3 |
2.5 |
48 |
0.0754 |
0.125 |
3881 |
2395 |
|
1x300 |
9.3 |
3.0 |
50 |
0.0601 |
0.100 |
4529 |
2672 |
|
1x400 |
9.3 |
3.0 |
53 |
0.0470 |
0.0778 |
5570 |
3094 |
|
1x500 |
9.3 |
3.0 |
55 |
0.0366 |
0.0605 |
6690 |
3595 |
Technical Characteristics of 26/35kV,26/35kV for CU or AL conductor/XLPE Insulated /PVC Sheathed Power Cable, 1-core
|
Nominal conductor cross section area (mm) |
Nominal Insulation thickness (mm) |
Nominal sheath thickness (mm) |
Approx Overall Diameter (mm) |
Max DC Conductor resistance at 20C (Ω/km) |
Approx weight of cable (kg/km) |
||
|
Cu |
Al |
Cu |
Al |
||||
|
1x50 |
10.5 |
2.2 |
39 |
0.387 |
0.641 |
1758 |
1449 |
|
1x70 |
10.5 |
2.4 |
41 |
0.268 |
0.443 |
2035 |
1604 |
|
1x95 |
10.5 |
2.4 |
43 |
0.193 |
0.320 |
2355 |
1767 |
|
1x 120 |
10.5 |
2.4 |
44 |
0.153 |
0.253 |
2666 |
1923 |
|
1x 150 |
10.5 |
2.5 |
46 |
0.124 |
0.206 |
3031 |
2103 |
|
1x 185 |
10.5 |
2.5 |
48 |
0.0991 |
0.164 |
3427 |
2282 |
|
1x240 |
10.5 |
2.6 |
50 |
0.0754 |
0.125 |
4070 |
2584 |
|
1x300 |
10.5 |
2.7 |
53 |
0.0601 |
0.100 |
4748 |
2891 |
|
1x400 |
10.5 |
2.8 |
56 |
0.0470 |
0.0778 |
5801 |
3325 |
|
1x500 |
10.5 |
2.9 |
59 |
0.0366 |
0.0605 |
6623 |
4076 |
Construction of 0.6/1kV 3-core for CU or AL conductor/XLPE Insulated /PVC Sheathed Power Cable

|
No |
Construction and materials |
|
1 |
Copper or aluminum conductor |
|
2 |
XLPE insulation |
|
3 |
PP yarn or glass fiber rope filler |
|
4 |
Non-woven cloth tape or glass fiber tape |
|
5 |
Non-flame retardant or flame retardant PVC outer sheath |
Technical Characteristics of 0.6/1kV for CU or AL conductor/XLPE Insulated /PVC Sheathed Power Cable, 3-core
|
Nominal conductor cross section area (mm) |
Nominal Insulation thickness (mm) |
Nominal sheath thickness (mm) |
Approx Overall Diameter (mm) |
Max DC Conductor resistance at 20C (Ω/km) |
Approx weight of cable (kg/km) |
||
|
Cu |
Al |
Cu |
Al |
||||
|
3x 1.5 |
0.7 |
1.5 |
10 |
12.1 |
--- |
145 |
--- |
|
3x2.5 |
0.7 |
1.5 |
11 |
7.41 |
12.1 |
185 |
140 |
|
3x4 |
0.7 |
1.5 |
12 |
4.61 |
7.41 |
250 |
175 |
|
3x6 |
0.7 |
1.5 |
13 |
3.08 |
4.61 |
320 |
210 |
|
3x10 |
0.7 |
1.5 |
15 |
1.83 |
3.08 |
450 |
260 |
|
3x16 |
0.7 |
1.5 |
17 |
1.15 |
1.91 |
640 |
340 |
|
3x25 |
0.9 |
2.0 |
21 |
0.727 |
1.20 |
940 |
470 |
|
3x35 |
0.9 |
2.0 |
23 |
0.524 |
0.868 |
1260 |
600 |
|
3x50 |
1.0 |
2.0 |
27 |
0.387 |
0.641 |
1670 |
730 |
|
3x70 |
1.1 |
2.0 |
30 |
0.268 |
0.443 |
2280 |
970 |
|
3x95 |
1.1 |
2.0 |
34 |
0.193 |
0.320 |
3020 |
1240 |
|
3x 120 |
1.2 |
2.5 |
38 |
0.153 |
0.253 |
3790 |
1540 |
|
3x 150 |
1.4 |
2.5 |
42 |
0.124 |
0.206 |
4750 |
1940 |
|
3x 185 |
1.6 |
2.5 |
45 |
0.0991 |
0.164 |
5654 |
2248 |
|
3x240 |
1.7 |
3.0 |
51 |
0.0754 |
0.125 |
7243 |
2723 |
Construction of 3.6/6kV to 26/35kV 3-core for CU or AL conductor/XLPE Insulated /PVC Sheathed Power Cable

|
No |
Construction and materials |
|
1 |
Copper or aluminum conductor |
|
2 |
Semi-conductive conductor screen |
|
3 |
XLPE insulation |
|
4 |
Semi-conductive insulation screen |
|
5 |
Copper tape screen |
|
6 |
PP yarn or glass fiber rope filler |
|
7 |
Non-woven cloth tape or glass fiber tape |
|
8 |
Non-flame retardant or flame retardant PVC outer sheath |
Technical Characteristics of 3.6/6kV for CU or AL conductor/XLPE Insulated /PVC Sheathed Power Cable, 3-core
|
Nominal conductor cross section area (mm) |
Nominal Insulation thickness (mm) |
Nominal sheath thickness (mm) |
Approx Overall Diameter (mm) |
Max DC Conductor resistance at 20C (Ω/km) |
Approx weight of cable (kg/km) |
||
|
Cu |
Al |
Cu |
Al |
||||
|
3x25 |
2.5 |
2.5 |
40 |
0.727 |
1.20 |
576 |
421 |
|
3x35 |
2.5 |
2.5 |
43 |
0.524 |
0.868 |
695 |
479 |
|
3x50 |
2.5 |
2.5 |
46 |
0.387 |
0.641 |
850 |
550 |
|
3x70 |
2.5 |
2.5 |
49 |
0.268 |
0.443 |
1081 |
648 |
|
3x95 |
2.5 |
3.0 |
53 |
0.193 |
0.320 |
1350 |
762 |
|
3x 120 |
2.5 |
3.0 |
57 |
0.153 |
0.253 |
1640 |
897 |
|
3x 150 |
2.5 |
3.0 |
61 |
0.124 |
0.206 |
1947 |
1019 |
|
3x 185 |
2.5 |
3.0 |
63 |
0.0991 |
0.164 |
2302 |
1152 |
|
3x240 |
2 6 |
3 5 |
70 |
0 0754 |
0 125 |
2886 |
1400 |
|
3x300 |
2.8 |
3.5 |
75 |
0.0601 |
0.100 |
3351 |
1626 |
Technical Characteristics of 6/6kV,6/10kV for CU or AL conductor/XLPE Insulated /PVC Sheathed Power Cable, 3-core
|
Nominal conductor cross section area (mm) |
Nominal Insulation thickness (mm) |
Nominal sheath thickness (mm) |
Approx Overall Diameter (mm) |
Max DC Conductor resistance at 20C (Ω/km) |
Approx weight of cable (kg/km) |
||
|
Cu |
Al |
Cu |
Al |
||||
|
3x25 |
3.4 |
2.5 |
42 |
0.727 |
1.20 |
1895 |
1430 |
|
3x35 |
3.4 |
2.5 |
44 |
0.524 |
0.868 |
2293 |
1640 |
|
3x50 |
3.4 |
2.5 |
46 |
0.387 |
0.641 |
2812 |
1881 |
|
3x70 |
3.4 |
3.0 |
50 |
0.268 |
0.443 |
3508 |
2205 |
|
3x95 |
3.4 |
3.0 |
54 |
0.193 |
0.320 |
4402 |
2635 |
|
3x 120 |
3.4 |
3.0 |
58 |
0.153 |
0.253 |
5319 |
3087 |
|
3x 150 |
3.4 |
3.0 |
62 |
0.124 |
0.206 |
6309 |
3518 |
|
3x 185 |
3.4 |
3.0 |
65 |
0.0991 |
0.164 |
7319 |
3877 |
|
3x240 |
3.4 |
3.5 |
71 |
0.0754 |
0.125 |
9218 |
4753 |
|
3x300 |
3.4 |
3.5 |
75 |
0.0601 |
0.100 |
11159 |
5577 |
Technical Characteristics of 8.7/10kV,8.7/15kV for CU or AL conductor/XLPE Insulated /PVC Sheathed Power Cable, 3-core
|
Nominal conductor cross section area (mm) |
Nominal Insulation thickness (mm) |
Nominal sheath thickness (mm) |
Approx Overall Diameter (mm) |
Max DC Conductor resistance at 20C (Ω/km) |
Approx weight of cable (kg/km) |
||
|
Cu |
Al |
Cu |
Al |
||||
|
3x25 |
4.5 |
2.8 |
50 |
0.727 |
1.20 |
2537 |
2072 |
|
3x35 |
4.5 |
2.9 |
53 |
0.524 |
0.868 |
2985 |
2334 |
|
3x50 |
4.5 |
2.9 |
55 |
0.387 |
0.641 |
3529 |
2598 |
|
3x70 |
4.5 |
2.9 |
58 |
0.268 |
0.443 |
4197 |
2895 |
|
3x95 |
4.5 |
3.3 |
63 |
0.193 |
0.320 |
5230 |
3462 |
|
3x 120 |
4.5 |
3.6 |
66 |
0.153 |
0.253 |
6120 |
3888 |
|
3x 150 |
4.5 |
3.6 |
70 |
0.124 |
0.206 |
7207 |
4416 |
|
3x 185 |
4.5 |
3.6 |
74 |
0.0991 |
0.164 |
8378 |
4935 |
|
3x240 |
4.5 |
3.6 |
79 |
0.0754 |
0.125 |
10177 |
5712 |
|
3x300 |
4.5 |
3.8 |
84 |
0.0601 |
0.100 |
12159 |
6577 |
Technical Characteristics of 12/20kV for CU or AL conductor/XLPE Insulated /PVC Sheathed Power Cable, 3-core
|
Nominal conductor cross section area (mm) |
Nominal Insulation thickness (mm) |
Nominal sheath thickness (mm) |
Approx Overall Diameter (mm) |
Max DC Conductor resistance at 20C (Ω/km) |
Approx weight of cable (kg/km) |
||
|
Cu |
Al |
Cu |
Al |
||||
|
3x35 |
5.5 |
3.0 |
57 |
0.524 |
0.868 |
3348 |
2696 |
|
3x50 |
5.5 |
3.0 |
60 |
0.387 |
0.641 |
3904 |
2973 |
|
3x70 |
5.5 |
3.0 |
63 |
0.268 |
0.443 |
4623 |
3321 |
|
3x95 |
5.5 |
3.5 |
67 |
0.193 |
0.320 |
5593 |
3825 |
|
3x 120 |
5.5 |
3.5 |
71 |
0.153 |
0.253 |
6495 |
4262 |
|
3x 150 |
5.5 |
3.5 |
74 |
0.124 |
0.206 |
7637 |
4846 |
|
3x 185 |
5.5 |
3.5 |
78 |
0.0991 |
0.164 |
8803 |
5361 |
|
3x240 |
5.5 |
3.5 |
84 |
0.0754 |
0.125 |
10729 |
6263 |
|
3x300 |
5.5 |
4.0 |
89 |
0.0601 |
0.100 |
12723 |
7141 |
Construction of 0.6/1kV 3-core, CU or AL conductor/XLPE Insulated/Steel Tape Armored/PVC Sheathed Power Cable

|
No |
Construction and materials |
|
1 |
Copper or aluminum conductor |
|
2 |
XLPE insulation |
|
3 |
PP yarn or glass fiber rope filler |
|
4 |
Non-woven cloth tape or glass fiber tape |
|
5 |
Non-flame retardant or flame retardant PVC bedding |
|
6 |
Steel tape armor |
|
7 |
Non-flame retardant or flame retardant PVC outer sheath |
Technical Characteristics for 12/20kV, CU or AL conductor/XLPE Insulated/ Steel Tape Armored/ PVC Sheathed Power Cable, 3-Core
|
Nominal conductor cross section area (mm) |
Nominal Insulation thickness (mm) |
Nominal sheath thickness (mm) |
Approx Overall Diameter (mm) |
Max DC Conductor resistance at 20C (Ω/km) |
Approx weight of cable (kg/km) |
||
|
Cu |
Al |
Cu |
Al |
||||
|
3x 10 |
0.7 |
1.5 |
18 |
1.83 |
3.08 |
622 |
433 |
|
3x 16 |
0.7 |
2.0 |
22 |
1.15 |
1.91 |
1005 |
705 |
|
3x25 |
0.9 |
2.0 |
25 |
0.727 |
1.20 |
1371 |
898 |
|
3x35 |
0.9 |
2.0 |
27 |
0.524 |
0.868 |
1724 |
1061 |
|
3x50 |
1.0 |
2.0 |
30 |
0.387 |
0.641 |
2247 |
1300 |
|
3x70 |
1.1 |
2.5 |
35 |
0.268 |
0.443 |
3023 |
1697 |
|
3x95 |
1.1 |
2.5 |
39 |
0.193 |
0.320 |
3825 |
2026 |
|
3x 120 |
1.2 |
2.5 |
42 |
0.153 |
0.253 |
4642 |
2370 |
|
3x 150 |
1.4 |
3.0 |
48 |
0.124 |
0.206 |
5767 |
2926 |
|
3x 185 |
1.6 |
3.0 |
51 |
0.0991 |
0.164 |
6896 |
3391 |
|
3x240 |
1.7 |
3.0 |
56 |
0.0754 |
0.125 |
8617 |
4072 |
Construction of 3.6/6kV to 26/35kV 3-core, CU or AL conductor/XLPE Insulated /Steel Tape Armored/PVC Sheathed Power Cable

|
No |
Construction and materials |
|
|
1 |
Copper or aluminum conductor |
|
|
2 |
Semi-conductive conductor screen |
|
|
3 |
XLPE insulation |
|
|
4 |
Semi-conductive insulation screen |
|
|
5 |
Copper tape screen |
|
|
6 |
PP yarn or glass fiber rope filler |
|
|
7 |
Non-woven cloth tape or glass fiber tape |
|
|
8 |
Non-flame retardant or flame retardant PVC bedding |
|
|
9 |
Steel tape/wire armor |
|
|
10 |
- |
PVC |
Technical Characteristics for 3.6/6kV, CU or AL conductor/ XLPE Insulated/ Steel Tape Armored/ PVC Sheathed Power Cable, 3-Core
|
Nominal conductor cross section area (mm) |
Nominal Insulation thickness (mm) |
Nominal sheath thickness (mm) |
Approx Overall Diameter (mm) |
Max DC Conductor resistance at 20C (Ω/km) |
Approx weight of cable (kg/km) |
||
|
Cu |
Al |
Cu |
Al |
||||
|
3x25 |
2.5 |
2.6 |
46 |
0.727 |
1.20 |
2945 |
2480 |
|
3x35 |
2.5 |
2.6 |
49 |
0.524 |
0.868 |
3390 |
2739 |
|
3x50 |
2.5 |
2.8 |
52 |
0.387 |
0.641 |
4065 |
3135 |
|
3x70 |
2.5 |
2.8 |
55 |
0.268 |
0.443 |
4816 |
3513 |
|
3x95 |
2.5 |
3.1 |
60 |
0.193 |
0.320 |
5897 |
4129 |
|
3x 120 |
2.5 |
3.1 |
63 |
0.153 |
0.253 |
6844 |
4611 |
|
3x 150 |
2.5 |
3.3 |
67 |
0.124 |
0.206 |
7973 |
5182 |
|
3x 185 |
2.5 |
3.5 |
71 |
0.0991 |
0.164 |
9281 |
5838 |
|
3x240 |
2.6 |
3.6 |
77 |
0.0754 |
0.125 |
11229 |
6763 |
|
3x300 |
2.8 |
3.7 |
83 |
0.0601 |
0.100 |
14106 |
8524 |
Technical Characteristics for 6.6/6kV, 6/10kV, CU or AL conductor/XLPE Insulated/Steel Tape Armored/PVC Sheathed Power Cable, 3-Core
|
Nominal conductor cross section area (mm) |
Nominal Insulation thickness (mm) |
Nominal sheath thickness (mm) |
Approx Overall Diameter (mm) |
Max DC Conductor resistance at 20C (Ω/km) |
Approx weight of cable (kg/km) |
||
|
Cu |
Al |
Cu |
Al |
||||
|
3x25 |
3.4 |
2.6 |
47 |
0.727 |
1.20 |
3010 |
2544 |
|
3x35 |
3.4 |
2.8 |
50 |
0.524 |
0.868 |
3498 |
2847 |
|
3x50 |
3.4 |
2.8 |
53 |
0.387 |
0.641 |
4135 |
3205 |
|
3x70 |
3.4 |
3.1 |
56 |
0.268 |
0.443 |
4958 |
3655 |
|
3x95 |
3.4 |
3.1 |
61 |
0.193 |
0.320 |
5974 |
4206 |
|
3x 120 |
3.4 |
3.2 |
64 |
0.153 |
0.253 |
6969 |
4736 |
|
3x 150 |
3.4 |
3.6 |
69 |
0.124 |
0.206 |
8161 |
5370 |
|
3x 185 |
3.4 |
3.6 |
72 |
0.0991 |
0.164 |
9417 |
5975 |
|
3x240 |
3.4 |
3.6 |
78 |
0.0754 |
0.125 |
11340 |
6874 |
|
3x300 |
3.4 |
3.8 |
84 |
0.0601 |
0.100 |
14247 |
8665 |
Technical Characteristics for 8.7/10kV,8.7/15kV,CU or AL conductor/XLPE Insulated/ Steel Tape Armored/ PVC Sheathed Power Cable, 3-Core
|
Nominal conductor cross section area (mm) |
Nominal Insulation thickness (mm) |
Nominal sheath thickness (mm) |
Approx Overall Diameter (mm) |
Max DC Conductor resistance at 20C (Ω/km) |
Approx weight of cable (kg/km) |
||
|
Cu |
Al |
Cu |
Al |
||||
|
3x25 |
4.5 |
2.9 |
53 |
0.727 |
1.20 |
3500 |
3035 |
|
3x35 |
4.5 |
2.9 |
55 |
0.524 |
0.868 |
3329 |
3329 |
|
3x50 |
4.5 |
3.1 |
58 |
0.387 |
0.641 |
4679 |
3748 |
|
3x70 |
4.5 |
3.1 |
61 |
0.268 |
0.443 |
5410 |
4107 |
|
3x95 |
4.5 |
3.4 |
66 |
0.193 |
0.320 |
6567 |
4799 |
|
3x 120 |
4.5 |
3.4 |
70 |
0.153 |
0.253 |
7541 |
5308 |
|
3x 150 |
4.5 |
3.6 |
73 |
0.124 |
0.206 |
8674 |
5883 |
|
3x 185 |
4.5 |
3.6 |
77 |
0.0991 |
0.164 |
9991 |
6549 |
|
3x240 |
4 5 |
4 0 |
84 |
0 0754 |
0 125 |
12887 |
8421 |
|
3x300 |
4.5 |
4.0 |
89 |
0.0601 |
0.100 |
14974 |
9392 |
Technical Characteristics for 12/20kV, CU or AL conductor/XLPE Insulated/ Steel Tape Armored/PVC Sheathed Power Cable, 3-Core
|
Nominal conductor cross section area (mm) |
Nominal Insulation thickness (mm) |
Nominal sheath thickness (mm) |
Approx Overall Diameter (mm) |
Max DC Conductor resistance at 20C (Ω/km) |
Approx weight of cable (kg/km) |
||
|
Cu |
Al |
Cu |
Al |
||||
|
3x35 |
5.5 |
3.2 |
63 |
0.524 |
0.868 |
4840 |
4189 |
|
3x50 |
5.5 |
3.2 |
66 |
0.387 |
0.641 |
5463 |
4532 |
|
3x70 |
5.5 |
3.3 |
69 |
0.268 |
0.443 |
6346 |
5044 |
|
3x95 |
5.5 |
3.6 |
74 |
0.193 |
0.320 |
7457 |
5689 |
|
3x 120 |
5.5 |
3.6 |
77 |
0.153 |
0.253 |
8459 |
6227 |
|
3x 150 |
5.5 |
3.8 |
82 |
0.124 |
0.206 |
10555 |
7764 |
|
3x 185 |
5.5 |
4.0 |
86 |
0.0991 |
0.164 |
11925 |
8483 |
|
3x240 |
5.5 |
4.0 |
92 |
0.0754 |
0.125 |
13959 |
9494 |
|
3x300 |
5.5 |
4.2 |
97 |
0.0601 |
0.100 |
16314 |
10731 |
Construction of 0.6/1kV 3-core, CU or AL conductor/XLPE Insulated/Steel Wire Armored/PVC Sheathed Power Cable

|
No |
Construction and materials |
|
1 |
Copper or aluminum conductor |
|
2 |
XLPE insulation |
|
3 |
PP yarn or glass fiber rope filler |
|
4 |
Non-woven cloth tape or glass fiber tape |
|
5 |
Non-flame retardant or flame retardant PVC bedding |
|
6 |
Steel wire armor |
|
7 |
Non-flame retardant or flame retardant PVC sheath |
Technical Characteristics for 0.6/1kV, CU or AL conductor/ XLPE Insulated/ Steel Wire Armored/PVC Sheathed Power Cable, 3-Core
|
Nominal conductor cross section area (mm) |
Nominal Insulation thickness (mm) |
Nominal sheath thickness (mm) |
Approx Overall Diameter (mm) |
Max DC Conductor resistance at 20C (Ω/km) |
Approx weight of cable (kg/km) |
||
|
Cu |
Al |
Cu |
Al |
||||
|
3x 10 |
0.7 |
2.0 |
21 |
1.83 |
3.08 |
820 |
630 |
|
3x 16 |
0.7 |
2.0 |
25 |
1.15 |
1.91 |
1450 |
1150 |
|
3x25 |
0.9 |
2.0 |
28 |
0.727 |
1.20 |
1850 |
1400 |
|
3x35 |
0.9 |
2.0 |
31 |
0.524 |
0.868 |
2300 |
1650 |
|
3x50 |
1.0 |
2.0 |
32 |
0.387 |
0.641 |
2650 |
1750 |
|
3x70 |
1.1 |
2.5 |
38 |
0.268 |
0.443 |
3650 |
2350 |
|
3x95 |
1.1 |
2.5 |
41 |
0.193 |
0.320 |
4550 |
2800 |
|
3x 120 |
1.2 |
3.0 |
43 |
0.153 |
0.253 |
5450 |
3200 |
|
3x 150 |
1.4 |
3.0 |
48 |
0.124 |
0.206 |
7000 |
4200 |
|
3x 185 |
1.6 |
3.0 |
58 |
0.0991 |
0.164 |
9328 |
5849 |
|
3x240 |
1.7 |
3.5 |
65 |
0.0754 |
0.125 |
11236 |
6587 |
Construction of 3.6/6kV to 26/35kV 3-core, CU or AL conductor/XLPE Insulated/Steel Wire Armored/PVC Sheathed Power Cable

|
No |
Construction and materials |
|
|
1 |
Copper or aluminum conductor |
|
|
2 |
Semi-conductive conductor screen |
|
|
3 |
XLPE insulation |
|
|
4 |
Semi-conductive insulation screen |
|
|
5 |
Copper tape screen |
|
|
6 |
PP yarn or glass fiber rope filler |
|
|
7 |
Non-woven cloth tape or glass fiber tape |
|
|
8 |
Non-flame retardant or flame retardant PVC bedding |
|
|
9 |
Steel wire armor |
|
|
10 |
- |
PVC |
Technical Characteristics for 3.6/6kV,CU or AL conductor/XLPE Insulated/Steel Wire Armored/PVC Sheathed Power Cable, 3-Core
|
Nominal conductor cross section area (mm) |
Nominal Insulation thickness (mm) |
Nominal sheath thickness (mm) |
Approx Overall Diameter (mm) |
Max DC Conductor resistance at 20C (Ω/km) |
Approx weight of cable (kg/km) |
||
|
Cu |
Al |
Cu |
Al |
||||
|
3x25 |
2.5 |
2.5 |
49 |
0.727 |
1.20 |
4246 |
3781 |
|
3x35 |
2.5 |
3.0 |
52 |
0.524 |
0.868 |
4770 |
4119 |
|
3x50 |
2.5 |
3.0 |
57 |
0.387 |
0.641 |
6194 |
5263 |
|
3x70 |
2.5 |
3.0 |
60 |
0.268 |
0.443 |
7092 |
5790 |
|
3x95 |
2.5 |
3.0 |
64 |
0.193 |
0.320 |
8263 |
6495 |
|
3x 120 |
2.5 |
3.5 |
68 |
0.153 |
0.253 |
9422 |
7190 |
|
3x 150 |
2.5 |
3.5 |
71 |
0.124 |
0.206 |
10667 |
7876 |
|
3x 185 |
2.5 |
3.5 |
76 |
0.0991 |
0.164 |
12113 |
8671 |
|
3x240 |
2.6 |
3.5 |
81 |
0.0754 |
0.125 |
14361 |
9895 |
|
3x300 |
2.8 |
3.5 |
87 |
0.0601 |
0.100 |
16632 |
11050 |
Technical Characteristics for 6.6/6kV,6/10kV, CU or AL conductor/XLPE Insulated/ Steel Wire Armored/PVC Sheathed Power Cable, 3-Core
|
Nominal conductor cross section area (mm) |
Nominal Insulation thickness
(mm) |
Nominal sheath thickness
(mm) |
Approx Overall Diameter
(mm) |
Max DC Conductor resistance at 20C (Ω/km) |
Approx weight of cable (kg/km) |
||
|
Cu |
Al |
Cu |
Al |
||||
|
3x25 |
3.4 |
3.0 |
50 |
0.727 |
1.20 |
4337 |
3872 |
|
3x35 |
3.4 |
3.0 |
53 |
0.524 |
0.868 |
4863 |
4212 |
|
3x50 |
3.4 |
3.0 |
58 |
0.387 |
0.641 |
6302 |
5371 |
|
3x70 |
3.4 |
3.0 |
61 |
0.268 |
0.443 |
7177 |
5875 |
|
3x95 |
3.4 |
3.5 |
65 |
0.193 |
0.320 |
8431 |
6663 |
|
3x 120 |
3.4 |
3.5 |
69 |
0.153 |
0.253 |
9559 |
7326 |
|
3x 150 |
3.4 |
3.5 |
73 |
0.124 |
0.206 |
10873 |
8246 |
|
3x 185 |
3.4 |
3.5 |
76 |
0.0991 |
0.164 |
12256 |
8814 |
|
3x240 |
3 4 |
3 5 |
82 |
0 0754 |
0 125 |
14509 |
10044 |
|
3x300 |
3.4 |
4.0 |
88 |
0.0601 |
0.100 |
16821 |
11239 |
Technical Characteristics for 8.7/10kV,8.7/15kV,CU or AL conductor/XLPE Insulated/ Steel Wire Armored/ PVC Sheathed Power Cable, 3-Core
|
Nominal conductor cross section area (mm) |
Nominal Insulation thickness
(mm) |
Nominal sheath thickness
(mm) |
Approx Overall Diameter
(mm) |
Max DC Conductor resistance at 20C (Ω/km) |
Approx weight of cable (kg/km) |
||
|
Cu |
Al |
Cu |
Al |
||||
|
3x25 |
4.5 |
3.2 |
60 |
0.727 |
1.20 |
6058 |
5593 |
|
3x35 |
4.5 |
3.2 |
63 |
0.524 |
0.868 |
6661 |
6010 |
|
3x50 |
4.5 |
3.2 |
66 |
0.387 |
0.641 |
7456 |
6525 |
|
3x70 |
4.5 |
3.4 |
69 |
0.268 |
0.443 |
8376 |
7074 |
|
3x95 |
4.5 |
3.4 |
73 |
0.193 |
0.320 |
9657 |
7890 |
|
3x 120 |
4.5 |
3.5 |
76 |
0.153 |
0.253 |
10834 |
8602 |
|
3x 150 |
4.5 |
3.8 |
81 |
0.124 |
0.206 |
12160 |
9369 |
|
3x 185 |
4.5 |
3.8 |
85 |
0.0991 |
0.164 |
13661 |
10219 |
|
3x240 |
4.5 |
4.2 |
91 |
0.0754 |
0.125 |
15992 |
11527 |
|
3x300 |
4.5 |
4.2 |
96 |
0.0601 |
0.100 |
18262 |
12680 |
Technical Characteristics for 12/20kV, CU or AL conductor/XLPE Insulated/ Steel Wire Armored/ PVC Sheathed Power Cable, 3-Core
|
Nominal conductor cross section area (mm) |
Nominal Insulation thickness (mm) |
Nominal sheath thickness (mm) |
Approx Overall Diameter (mm) |
Max DC Conductor resistance at 20C (Ω/km) |
Approx weight of cable (kg/km) |
||
|
Cu |
Al |
Cu |
Al |
||||
|
3x35 |
5.5 |
3.5 |
68 |
0.524 |
0.868 |
7430 |
6752 |
|
3x50 |
5.5 |
3.5 |
70 |
0.387 |
0.641 |
8139 |
7208 |
|
3x70 |
5.5 |
3.5 |
74 |
0.268 |
0.443 |
9133 |
7831 |
|
3x95 |
5.5 |
3.5 |
78 |
0.193 |
0.320 |
10450 |
8682 |
|
3x 120 |
5.5 |
3.5 |
82 |
0.153 |
0.253 |
11612 |
9379 |
|
3x 150 |
5.5 |
4.0 |
86 |
0.124 |
0.206 |
12982 |
10191 |
|
3x 185 |
5.5 |
4.0 |
89 |
0.0991 |
0.164 |
14540 |
11098 |
|
3x240 |
5.5 |
4.0 |
95 |
0.0754 |
0.125 |
16751 |
12285 |
|
3x300 |
5.5 |
4.0 |
101 |
0.0601 |
0.100 |
19242 |
13660 |