Lighting & electrical

GKC433M Circuit Breaker Analyzer

<p>1. Test the mechanical and electrical characteristics of various high-voltage circuit breakers, isolating switches, and contactors.<br/></p><p>2. Test parameters such as closing time, opening time, asynchronous time, bounce time, pre insertion time, and cooperating time for 12 main contacts, 6 contacts with closing resistors, 6 main contacts, and 6 auxiliary contacts.</p>

SupplierShiJiaZhuang Handy Technology Co.,Ltdwww.handy-china.com
Source categories

About this product

Product information from the supplier.

INSTRUCTION

1. Test the mechanical and electrical characteristics of various high-voltage circuit breakers, isolating switches, and contactors.

2. Test parameters such as closing time, opening time, asynchronous time, bounce time, pre insertion time, and cooperating time for 12 main contacts, 6 contacts with closing resistors, 6 main contacts, and 6 auxiliary contacts.

3. Measure the pre-insert time and resistance of 6 resistor contacts.

4. The instrument interface is equipped with 12 contact status indicators, which facilitate the judgment of the closing and opening status and check whether the wiring is correct.


FEATURES

1. Test the mechanical and electrical characteristics of various high-voltage circuit breakers, isolating switches, and contactors.

2. Test parameters such as closing time, opening time, asynchronous time, bounce time, pre insertion time, and cooperating time for 12 main contacts, 6 contacts with closing resistors, 6 main contacts, and 6 auxiliary contacts.

3. Measure the pre-insert time and resistance of 6 resistor contacts.

4. The instrument interface is equipped with 12 contact status indicators, which facilitate the judgment of the closing and opening status and check whether the wiring is correct.

5. Equipped with one analog transducer input channel and one digital transducer input channel. It can measure the stroke, penetration, rebound, overshoot time, overshoot and speed of switchgear through resistive transducers and digital transducers.

6. Digital transducers can accurately measure the rotation angle of single-turn or multi-turn operating mechanisms, with a measurement resolution up to 0.05 degrees, providing data basis for judging whether the switch operates in place.

7. Support closing, opening, O-C-O, C-O and O-C control modes.

8. Capable of testing mechanical characteristics of manually operated circuit breakers.

9. Support editing and storing 50 switch models with customized speed definitions.

10. Support speed definition modification and data recalculation after test completion.

11. Built-in high-power adjustable DC power supply, equipped with a manual voltage adjustment knob, closing button and opening button, enabling rapid closing/opening operation and operating voltage test.

12. The built-in continuously output DC power supply is applied to motor energy storage.

13. Support motor current measurement. By analyzing the motor current of circuit breakers or isolating switches, it can judge abnormal conditions of the circuit breaker energy storage system or isolating switch motion system.

14. Adopt electronic switches for output control, featuring high control accuracy and long service life.

15. Built-in current sensors are used to measure the current of closing coils and opening coils.

16. The instrument can store 500 sets of test data with power-off protection function (no data loss after power failure).

17. Stored test data can be exported via USB flash drive.

18. Support instrument internal software upgrade via USB flash drive.

19. Equipped with an LCD screen, which can clearly display the operation interface, test data, contact waveform, travel curve and current curve both indoors and outdoors.

21. Equipped with a high-speed thermal printer to output test data, contact waveforms, travel curves and current curves.

22. Support up to 10,000 automatic operation tests.

23. Support computer connection and operation via USB communication cable.

24. Test data can be opened on a computer for analysis, envelope generation and test report generation.

25. Reserved communication interfaces, supporting optional external modules including dynamic resistance measurement, double-side grounding test and graphite contact test.

26. Support online testing and internal test data extraction via Bluetooth 2.0 and above devices (optional).


SPECIFICATIONS:

Time Measurement Range: 1~20000ms. Accuracy: ±(0.05%t+0.1)ms

1~10000ms, resolution 0.1ms; 10000~20000ms, resolution 0.2ms

Sampling Frequency: 1~10000ms: 10kHz; 10000~20000ms: 5kHz

Analog Sensor Input Measurement Range: 0~5V

Analog Sensor Resistance Range: 50Ω~5kΩ

Digital Sensor Interface: Long-line driver RS422 interface

Digital Sensor Angle Measurement Accuracy: ±0.1º, resolution: 0.05º

Stroke Measurement Range depends on sensor length. Up to 1000mm. Minimum resolution 0.1mm

Stroke Measurement Accuracy: ±(0.5%L+0.2)mm

Speed Measurement Range: 0~20m/s, resolution 0.01m/s

DC Power Supply Output: 10~270V/20A, power 3kW

DC Voltmeter Measurement Range: 0~300V, accuracy: ±(0.5%U+1)V

Coil Current Measurement: DC 0~3A~30A, AC peak 0~3A~30A, resolution: 0.01A

Motor Current Measurement: DC 0~4A~40A, AC peak 0~4A~40A, resolution: 0.01A

Closing Resistor Measurement Range: 50~2000Ω; resolution 0.1Ω, accuracy ±(1%R+1)Ω

Trigger Start Voltage: ≥30V

Output Control Power: 300V DC/AC, 30A DC/AC

Power Supply: 198~264V AC, 47~63Hz

Operating Conditions: Temperature -10℃~50℃, Humidity ≤90%RH, non-condensing

Dimensions: 427mm×357mm×193mm